Number
Size (Bytes)
Default Value
Name
Description
1
1
0
In-wall Switch Type for Load to control I1
With this parameter, you can select between push-button (momentary) and on/off toggle switch types.
11
2
0
Turn Load 1 Off Automatically with Timer
If Load is ON, you can schedule it to turn OFF automatically after a period of time defined in this parameter. The timer is reset to zero each time the device receives an ON or OFF command, either remotely (from the gateway (hub) or associated device) or locally from the switch.
12
2
0
Turn Load 1 On Automatically with Timer
If Load is OFF, you can schedule it to turn ON automatically after a period of time defined in this parameter. The timer is reset to zero each time the device receives an OFF or ON command, either remotely (from the gateway (hub) or associated device) or locally from the switch.
21
1
0
Enable/Disable the Double click function
If the Double click function is enabled, a fast double click on the push-button will set the dimming level to the maximum dimming value.
30
1
0
Restore on/off status for load after power failure
This parameter determines if on/off status is saved and restored for the load after power failure.
40
1
10
Watt Power Consumption Reporting Threshold for Load
Choose by how much the power consumption needs to increase or decrease to be reported. Values correspond to percentages so if 10 is set (by default), the device will report any power consumption changes of 10% or more compared to the last reading.
ⓘ NOTE: The power consumption needs to increase or decrease by at least 2 Watts to be reported, regardless of percentage set in this parameter.
42
2
0
Watt Power Consumption Reporting Time Threshold for Load
Set value refers to the time interval with which power consumption in Watts is reported (0 – 32767 seconds). If 300 is entered, energy consumption reports will be sent to the gateway (hub) every 300 seconds (or 5 minutes) if there was a change compared from the last report.
ⓘNOTE: Values from 1 to 29 are ignored by device due to standard recommendation.
ⓘNOTE: The report will be send only if there was a change compared to the last report.
5
1
0
Working mode
With this parameter, you can change the device presentation on the user interface.
ⓘ NOTE: After parameter change, first exclude the device (without setting parameters to default value) then wait at least 30s before reinclusion.
60
1
0
Minimum dimming value
The value set in this parameter determines the minimum dimming value (the lowest value which can be set on the device, when, for example, dimming lights with wall switch or slider in the GUI (Gateway - hub)) (Data type 1 byte dec)
• default value 0 = 0% (minimum dimming value)
• 0- 98 = 0% - 98%, step is 1%. Minimum dimming value is set by entering a value.
ⓘ NOTE: The minimum level may not be higher than the maximum level!
61
1
99
Maximum dimming value
The value set in this parameter determines the maximum dimming value (the highest value which can be set on the device, when, for example, dimming lights with wall switch or slider in the GUI (Gateway - hub))
ⓘ NOTE: The maximum level may not be lower than the minimum level!
65
1
1
Dimming time when key pressed (soft on/off)
Choose the time during which the device will move between the min. and max. dimming values by a short press of the push-button I1.
66
2
3
Dimming time when key hold
Choose the time during which the Dimmer will move between the min. and max. dimming values during a continuous press of the push-button I1, by an associated device or through the UI controls (BasicSet, SwitchMultilevelSet).
67
1
0
Ignore start level
Choose whether the device should use (or disregard) the start dimming level value. If the device is configured to use the start level, it should start the dimming process from the currently set dimming level. This parameter is used with association group 3.
NOTE: Parameter is valid only in Dimmer mode. In Switch mode the parameter has no effect.
68
1
0
Dimming duration
Choose the time during which the device will transition from the current value to the new target value. This parameter applies to the association group 3.
NOTE: Parameter is valid only in Dimmer mode. In Switch mode the parameter has no effect.
70
2
200
Overload safety switch
The function allows for turning off the controlled device in case of exceeding the defined power for more than 5s. Controlled device can be turned back on by input I1 or sending a control frame.
ⓘ NOTE: This functionality is not an overload safety protection, please check the technical specifications chapter for more details.
In case of overload the following message will be send towards the controller:
• COMMAND_CLASS_NOTIFICATION_V5
• The Alarm V1 type field set to 0x00
• Notification Type 0x08 and 0x08 (Overload detected)
71
1
0
Calibration trigger
Choose when will be the calibration procedure triggered.
72
1
2
Calibration status (read only)
With this parameter you can check the calibration status.
73
1
0
Alarm/Notification events
This parameter defines the module behaviour in case it receives any Alarm/Notification events.
NOTE: When value 3 is selected the default time interval of the blinking is 10 minutes. It can be stopped with a button press or sending a control frame. To adjust the time interval please refer to parameter 74 – Alarm/Notification time interval.
74
1
10
Alarm/Notification time interval (dependant on parameter 73)
This parameter defines the time interval of the blinking state, once the module receives an alarm/notification event. Minimum step increase is 1 minute.
NOTE: This parameter does not have any effect if parameter 73 is not set to value 3.